FireLite MRP-2002E

  • Image 1
Price:
Contact us on 021-68880295-97
Bookmark and Share


Product Description

DF-60238:A2 • 02/05/08
MRP-2002(E)
Agent Release Control Panel
Conventional
DF-60238:A2 • A2-350
General
The MRP-2002 is a six-zone FACP for single and dual hazard
agent releasing applications. The MRP-2002 provides reliable
fire detection, signaling and protection for commercial, indus-
trial and institutional buildings requiring agent-based releasing.
The MRP-2002 is compatible with System Sensor’s i3 detec-
tors which are conventional smoke detectors that can transmit
a maintenance trouble signal to the FACP indicating the need
for cleaning and a supervisory ‘freeze’ signal when the ambi-
ent  temperature  falls  below  the  detector  rating  of  approxi-
mately   45°F   (7.22°C).   In   addition,   the   control   panel   is
compatible  with  conventional  input  devices  such  as  two-wire
smoke  detectors,  four-wire  smoke  detectors,  pull  stations,
waterflow  devices,  tamper  switches  and  other  normally-open
contact  devices.  Refer  to  the  Fire•Lite  Device  Compatibility
Document for a complete listing of compatible devices.
Four  outputs  are  programmable  as  NACs  (Notification  Appli-
ance  Circuits)  or  releasing  circuits.  Three  programmable
Form-C  relays  (factory  programmed  for  Alarm,  Trouble  and
Supervisory)  and  24  VDC  special  application  resettable  and
non-resettable  power  outputs  are  also  included  on  the  main
circuit board. The MRP-2002 supervises all wiring, AC voltage,
battery charger and battery level.
Activation  of  a  compatible  smoke  detector  or  any  normally-
open fire alarm initiating device will activate audible and visual
signaling devices, illuminate an indicator, display alarm infor-
mation  on  the  panel’s  LCD,  sound  the  piezo  sounder  at  the
FACP, activate the FACP alarm relay and operate an optional
module used to notify a remote station or initiate an auxiliary
control function.
The  MRP-2002E  offers  the  same  features  as  the  MRP-2002
but allows connection to 220/240 VAC. Unless otherwise spec-
ified, the information in this data sheet applies to both the 110/
120 VAC and 220/240 VAC versions of the panels.
Features
•   Listed to UL Standard 864, 9th edition.
•   Designed  for  agent  releasing  standards  NFPA  12,  12A,
12B, and 2001.
•   Disable/Enable control per input zone and output zone.
•   Extensive transient protection.
•   Dual hazard operation.
•   Adjustable  pre-discharge,  discharge  and  waterflow  delay
timers.
•   Cross-zone (double-interlock) capability.
•   Six programmable Style B (Class B) IDCs (Initiating Device
Circuit).
•   System Sensor i3 series detector compatible.
•   Four programmable Style Y (Class B) output circuits - (spe-
cial application power).
•   Strobe synchronization:
– System Sensor
– Wheelock
– Gentex
– Faraday
– Amseco
•   Three programmable Form-C relays.
•   7.0 amps total 24 VDC output current.
•   Resettable and non-resettable output power.
•   Built-in Programmer.
•   ANN-BUS for connection to optional (up to 8 total of any of
the following):
– ANN-80 Remote LCD Annunciator
– ANN-I/O LED Driver
– ANN-S/PG Printer Module
– ANN-RLY Relay Module
– ANN-LED Annunciator Module
•   80-character LCD display (backlit).
•   Real-time clock/calendar with daylight savings time control.
•   History log with 256 event storage.
•   Piezo sounder for alarm, trouble and supervisory.
•   24 volt operation.
•   Low AC voltage sense.
•   Outputs Programmable for:
– Releasing Circuits or NACS
•   NACs programmable for:
– Silence Inhibit
– Auto-Silence
– Strobe Synchronization
– Selective Silence (horn-strobe mute)
– Temporal or Steady Signal
– Silenceable or Non-silenceable
– Release Stage Sounder
•   Automatic battery charger with charger supervision.
•   Optional Dress Panel DP-51050 (red).Page 2 of 4 — DF-60238:A2 • 02/05/08
•   Optional Trim Ring TR-CE (red) for semi-flush mounting the
cabinet.
•   Optional  CAC-5X  Class  A  Converter  Module  for  Outputs
and IDCs.
•   Optional 4XTMF Municipal Box Transmitter Module.
•   Optional Digital Alarm Communicators (411, 411UD, 
411UDAC).
PROGRAMMING AND SOFTWARE:
•   Custom English labels (per point) may be manually entered
or selected from an internal library file.
•   Programmable Abort operation.
•   Three programmable Form-C relay outputs.
•   Pre-programmed and custom application templates.
•   Continuous fire protection during online programming at the
front panel.
•   Program  Check  automatically  catches  common  errors  not
linked to any zone or input point.
USER INTERFACE:
•   Integral 80-character LCD display with backlighting.
•   Real-time  clock/calendar  with  automatic  daylight  savings
adjustments.
•   ANN-Bus for connection to remote annunciators.
•   Audible or silent walk test capabilities.
•   Piezo sounder for alarm, trouble, and supervisory.
Controls and Indicators
LED INDICATORS
•   FIRE ALARM (red).
•   SUPERVISORY (yellow).
•   TROUBLE (yellow).
•   AC POWER (green).
•   ALARM SILENCED (yellow).
•   DISCHARGED (red).
•   PRE-DISCHARGE (red indicator).
•   ABORT (yellow indicator).
CONTROL BUTTONS
•   ACKNOWLEDGE.
•   ALARM SILENCE.
•   SYSTEM RESET (lamp test).
•   DRILL.
AC Power – TB1 
•   MRP-2002: 120 VAC, 50/60 Hz, 2.3 amps.
•   MRP-2002E: 240 VAC, 50 Hz, 1.15 amps.
•   Wire size: minimum #14 AWG (2.0 mm2) with 600V insula-
tion.
•   Supervised, nonpower-limited.
Battery (sealed lead acid only) – J12: 
•   Maximum  Charging  Circuit  -  Normal  Flat  Charge:  27.6
VDC @ 1.4 amp. Supervised, nonpower-limited.
•   Maximum  Charger  Capacity:  26  Amp  Hour  battery  (two
18 Amp Hour batteries can be housed in the FACP cabinet.
Larger  batteries  require  separate  battery  box  such  as  the
BB-26 or BB-55). 
•   Minimum Battery Size: 7 Amp Hour.
Initiating Device Circuits - TB4 and TB6
•   Alarm Zones 1 - 5 on TB4.
•   Alarm Zone 6 on TB6.
•   Supervised and power-limited circuitry.
•   Style B (Class B) wiring with Style D (Class A) option.
•   Normal Operating Voltage: Nominal 20 VDC.
•   Alarm Current: 15 mA minimum.
•   Short Circuit Current: 40 mA max.
•   Maximum Loop Resistance: 100 Ohms.
•   End-of-Line Resistor: 4.7KOhms, 1/2 watt (PN 71252).
•   Standby Current: 4 mA.
Refer to the Fire•Lite Device Compatibility Document for listed
compatible devices.
Notification Appliance and Releasing Circuit(s) - TB5 and
TB7
•   Four Output Circuits.
•   Style  Y  (Class  B)  or  Style  Z  (Class  A)  with  optional  con-
verter module.
•   Special Application power.
•   Supervised and power-limited circuitry.
•   Normal Operating Voltage: Nominal 24 VDC.
•   Maximum Signaling Current: 7.0 amps (3.0 amps maximum
per NAC).
•   End-of-Line Resistor: 4.7KOhms, 1/2 watt (PN 71252).
•   Max. Wiring Voltage Drop: 2 VDC.
Refer to the Fire•Lite Device Compatibility Document for com-
patible listed devices.
Form-C Relays - Programmable - TB8
•   Relay 1 (factory default programmed as Alarm Relay)
•   Relay  2  (factory  default  programmed  as  fail-safe  Trouble
Relay)
•   Relay 3 (factory default programmed as Supervisory Relay)
•   Relay Contact Ratings: 
– 2 amps @ 30 VDC (resistive)
– 2 amps @ 30 VAC (resistive)
Auxiliary Trouble Input – J6
The  Auxiliary  Trouble  Input  is  an open  collector circuit  which
can be used to monitor external devices for trouble conditions.
It can be connected to the trouble bus of a peripheral, such as
a  power  supply,  which  is  compatible  with  open  collector  cir-
cuits.
Special Application Resettable Power - TB9
•   Operating Voltage: Nominal 24 VDC.
•   Maximum  Available  Current:  500  mA  -  appropriate  for
powering 4-wire smoke detectors (see note).
•   Power-limited Circuitry.
Refer to the Fire•Lite Device Compatibility Document for com-
patible listed devices.
NOTE: Total current for resettable power, nonresettable power and
Output Circuits must not exceed 7.0 amps.
Special  Application  Resettable  or  Nonresettable  Power  -
TB9
•   Operating Voltage: Nominal 24 VDC.
•   Maximum Available Current: 500 mA (see note 1).
•   Power-limited Circuitry.
•   Jumper selectable by JP31 for resettable or nonresettable
power:.
Refer to the Fire•Lite Device Compatibility Document for com-
patible listed devices.Product Line Information
MRP-2002:  Six-zone,  24  volt  Agent  Release  Control  Panel
(includes  backbox,  power  supply,  technical  manual,  and  a
frame  &  post  operating  instruction  sheet)  for  single  and  dual
hazard agent releasing applications.
MRP-2002E:  Same  as  above  but  allows  connection  to  220/
240 VAC.
CAC-5X:  Class  A  Converter  Module  can  be  used  to  convert
the  Style  B  (Class  B)  Initiating  Device  Circuits  to  Style  D
(Class  A)  and  Style  Y  (Class  B)  Output  Circuits  to  Style  Z
(Class A). 
NOTE: Two Class A Converter modules are required to convert all
four Output Circuits and six Initiating Device Circuits.
4XTMF: Transmitter Module provides a supervised output for
local energy municipal box transmitter and alarm and trouble
reverse polarity. It includes a disable switch and disable trouble
LED. 
ANN-80: LCD Annunciator is a remote LCD annunciator that
mimics  the  information  displayed  on  the  FACP  LCD  display.
Recommended wire type is un-shielded.
ANN-LED: Annunciator Module provides three LEDs for each
zone: Alarm, Trouble and Supervisory.  Ships with enclosure
(red and black enclosures available; refer to DF-60241).  
ANN-RLY:  Relay  Module,  which  can  be  mounted  inside  the
cabinet, provides 10 programmable Form-C relays.
ANN-S/PG: Serial/Parallel Printer Gateway module provides a
connection for a serial or parallel printer.
ANN-I/O: LED Driver Module provides connections to a user
supplied graphic annunciator.
DP-51050:  Dress  panel  (red)  is  available  as  an  option.  The
dress panel restricts access to the system wiring while allow-
ing access to the membrane switch panel.
TR-CE: Trim-ring (red) is available as an option. The trim-ring
allows semi-flushing mounting of the cabinet.
BB-26:  Battery  box,  holds  up  to  two  26  Amp  Hour  batteries
and CHG-75.
BB-55: Battery box, houses two 55 Amp Hour batteries.
BAT Series Batteries: Refer to DF-52397.
PRN-6F:  UL-listed  compatible  event  printer.  Dot-matrix,  trac-
tor-fed paper, 120 VAC.
PRT-PK-CABLE:  Programming  cable.  Used  to  update  the
FACP’s  flash  firmware.  (Also  requires  an  RS485  to  RS232
converter).