DF-60238:A2 • 02/05/08
MRP-2002(E)
Agent Release Control Panel
Conventional
DF-60238:A2 • A2-350
General
The MRP-2002 is a six-zone FACP for single and dual hazard
agent releasing applications. The MRP-2002 provides reliable
fire detection, signaling and protection for commercial, indus-
trial and institutional buildings requiring agent-based releasing.
The MRP-2002 is compatible with System Sensor’s i3 detec-
tors which are conventional smoke detectors that can transmit
a maintenance trouble signal to the FACP indicating the need
for cleaning and a supervisory ‘freeze’ signal when the ambi-
ent temperature falls below the detector rating of approxi-
mately 45°F (7.22°C). In addition, the control panel is
compatible with conventional input devices such as two-wire
smoke detectors, four-wire smoke detectors, pull stations,
waterflow devices, tamper switches and other normally-open
contact devices. Refer to the Fire•Lite Device Compatibility
Document for a complete listing of compatible devices.
Four outputs are programmable as NACs (Notification Appli-
ance Circuits) or releasing circuits. Three programmable
Form-C relays (factory programmed for Alarm, Trouble and
Supervisory) and 24 VDC special application resettable and
non-resettable power outputs are also included on the main
circuit board. The MRP-2002 supervises all wiring, AC voltage,
battery charger and battery level.
Activation of a compatible smoke detector or any normally-
open fire alarm initiating device will activate audible and visual
signaling devices, illuminate an indicator, display alarm infor-
mation on the panel’s LCD, sound the piezo sounder at the
FACP, activate the FACP alarm relay and operate an optional
module used to notify a remote station or initiate an auxiliary
control function.
The MRP-2002E offers the same features as the MRP-2002
but allows connection to 220/240 VAC. Unless otherwise spec-
ified, the information in this data sheet applies to both the 110/
120 VAC and 220/240 VAC versions of the panels.
Features
• Listed to UL Standard 864, 9th edition.
• Designed for agent releasing standards NFPA 12, 12A,
12B, and 2001.
• Disable/Enable control per input zone and output zone.
• Extensive transient protection.
• Dual hazard operation.
• Adjustable pre-discharge, discharge and waterflow delay
timers.
• Cross-zone (double-interlock) capability.
• Six programmable Style B (Class B) IDCs (Initiating Device
Circuit).
• System Sensor i3 series detector compatible.
• Four programmable Style Y (Class B) output circuits - (spe-
cial application power).
• Strobe synchronization:
– System Sensor
– Wheelock
– Gentex
– Faraday
– Amseco
• Three programmable Form-C relays.
• 7.0 amps total 24 VDC output current.
• Resettable and non-resettable output power.
• Built-in Programmer.
• ANN-BUS for connection to optional (up to 8 total of any of
the following):
– ANN-80 Remote LCD Annunciator
– ANN-I/O LED Driver
– ANN-S/PG Printer Module
– ANN-RLY Relay Module
– ANN-LED Annunciator Module
• 80-character LCD display (backlit).
• Real-time clock/calendar with daylight savings time control.
• History log with 256 event storage.
• Piezo sounder for alarm, trouble and supervisory.
• 24 volt operation.
• Low AC voltage sense.
• Outputs Programmable for:
– Releasing Circuits or NACS
• NACs programmable for:
– Silence Inhibit
– Auto-Silence
– Strobe Synchronization
– Selective Silence (horn-strobe mute)
– Temporal or Steady Signal
– Silenceable or Non-silenceable
– Release Stage Sounder
• Automatic battery charger with charger supervision.
• Optional Dress Panel DP-51050 (red).Page 2 of 4 — DF-60238:A2 • 02/05/08
• Optional Trim Ring TR-CE (red) for semi-flush mounting the
cabinet.
• Optional CAC-5X Class A Converter Module for Outputs
and IDCs.
• Optional 4XTMF Municipal Box Transmitter Module.
• Optional Digital Alarm Communicators (411, 411UD,
411UDAC).
PROGRAMMING AND SOFTWARE:
• Custom English labels (per point) may be manually entered
or selected from an internal library file.
• Programmable Abort operation.
• Three programmable Form-C relay outputs.
• Pre-programmed and custom application templates.
• Continuous fire protection during online programming at the
front panel.
• Program Check automatically catches common errors not
linked to any zone or input point.
USER INTERFACE:
• Integral 80-character LCD display with backlighting.
• Real-time clock/calendar with automatic daylight savings
adjustments.
• ANN-Bus for connection to remote annunciators.
• Audible or silent walk test capabilities.
• Piezo sounder for alarm, trouble, and supervisory.
Controls and Indicators
LED INDICATORS
• FIRE ALARM (red).
• SUPERVISORY (yellow).
• TROUBLE (yellow).
• AC POWER (green).
• ALARM SILENCED (yellow).
• DISCHARGED (red).
• PRE-DISCHARGE (red indicator).
• ABORT (yellow indicator).
CONTROL BUTTONS
• ACKNOWLEDGE.
• ALARM SILENCE.
• SYSTEM RESET (lamp test).
• DRILL.
AC Power – TB1
• MRP-2002: 120 VAC, 50/60 Hz, 2.3 amps.
• MRP-2002E: 240 VAC, 50 Hz, 1.15 amps.
• Wire size: minimum #14 AWG (2.0 mm2) with 600V insula-
tion.
• Supervised, nonpower-limited.
Battery (sealed lead acid only) – J12:
• Maximum Charging Circuit - Normal Flat Charge: 27.6
VDC @ 1.4 amp. Supervised, nonpower-limited.
• Maximum Charger Capacity: 26 Amp Hour battery (two
18 Amp Hour batteries can be housed in the FACP cabinet.
Larger batteries require separate battery box such as the
BB-26 or BB-55).
• Minimum Battery Size: 7 Amp Hour.
Initiating Device Circuits - TB4 and TB6
• Alarm Zones 1 - 5 on TB4.
• Alarm Zone 6 on TB6.
• Supervised and power-limited circuitry.
• Style B (Class B) wiring with Style D (Class A) option.
• Normal Operating Voltage: Nominal 20 VDC.
• Alarm Current: 15 mA minimum.
• Short Circuit Current: 40 mA max.
• Maximum Loop Resistance: 100 Ohms.
• End-of-Line Resistor: 4.7KOhms, 1/2 watt (PN 71252).
• Standby Current: 4 mA.
Refer to the Fire•Lite Device Compatibility Document for listed
compatible devices.
Notification Appliance and Releasing Circuit(s) - TB5 and
TB7
• Four Output Circuits.
• Style Y (Class B) or Style Z (Class A) with optional con-
verter module.
• Special Application power.
• Supervised and power-limited circuitry.
• Normal Operating Voltage: Nominal 24 VDC.
• Maximum Signaling Current: 7.0 amps (3.0 amps maximum
per NAC).
• End-of-Line Resistor: 4.7KOhms, 1/2 watt (PN 71252).
• Max. Wiring Voltage Drop: 2 VDC.
Refer to the Fire•Lite Device Compatibility Document for com-
patible listed devices.
Form-C Relays - Programmable - TB8
• Relay 1 (factory default programmed as Alarm Relay)
• Relay 2 (factory default programmed as fail-safe Trouble
Relay)
• Relay 3 (factory default programmed as Supervisory Relay)
• Relay Contact Ratings:
– 2 amps @ 30 VDC (resistive)
– 2 amps @ 30 VAC (resistive)
Auxiliary Trouble Input – J6
The Auxiliary Trouble Input is an open collector circuit which
can be used to monitor external devices for trouble conditions.
It can be connected to the trouble bus of a peripheral, such as
a power supply, which is compatible with open collector cir-
cuits.
Special Application Resettable Power - TB9
• Operating Voltage: Nominal 24 VDC.
• Maximum Available Current: 500 mA - appropriate for
powering 4-wire smoke detectors (see note).
• Power-limited Circuitry.
Refer to the Fire•Lite Device Compatibility Document for com-
patible listed devices.
NOTE: Total current for resettable power, nonresettable power and
Output Circuits must not exceed 7.0 amps.
Special Application Resettable or Nonresettable Power -
TB9
• Operating Voltage: Nominal 24 VDC.
• Maximum Available Current: 500 mA (see note 1).
• Power-limited Circuitry.
• Jumper selectable by JP31 for resettable or nonresettable
power:.
Refer to the Fire•Lite Device Compatibility Document for com-
patible listed devices.Product Line Information
MRP-2002: Six-zone, 24 volt Agent Release Control Panel
(includes backbox, power supply, technical manual, and a
frame & post operating instruction sheet) for single and dual
hazard agent releasing applications.
MRP-2002E: Same as above but allows connection to 220/
240 VAC.
CAC-5X: Class A Converter Module can be used to convert
the Style B (Class B) Initiating Device Circuits to Style D
(Class A) and Style Y (Class B) Output Circuits to Style Z
(Class A).
NOTE: Two Class A Converter modules are required to convert all
four Output Circuits and six Initiating Device Circuits.
4XTMF: Transmitter Module provides a supervised output for
local energy municipal box transmitter and alarm and trouble
reverse polarity. It includes a disable switch and disable trouble
LED.
ANN-80: LCD Annunciator is a remote LCD annunciator that
mimics the information displayed on the FACP LCD display.
Recommended wire type is un-shielded.
ANN-LED: Annunciator Module provides three LEDs for each
zone: Alarm, Trouble and Supervisory. Ships with enclosure
(red and black enclosures available; refer to DF-60241).
ANN-RLY: Relay Module, which can be mounted inside the
cabinet, provides 10 programmable Form-C relays.
ANN-S/PG: Serial/Parallel Printer Gateway module provides a
connection for a serial or parallel printer.
ANN-I/O: LED Driver Module provides connections to a user
supplied graphic annunciator.
DP-51050: Dress panel (red) is available as an option. The
dress panel restricts access to the system wiring while allow-
ing access to the membrane switch panel.
TR-CE: Trim-ring (red) is available as an option. The trim-ring
allows semi-flushing mounting of the cabinet.
BB-26: Battery box, holds up to two 26 Amp Hour batteries
and CHG-75.
BB-55: Battery box, houses two 55 Amp Hour batteries.
BAT Series Batteries: Refer to DF-52397.
PRN-6F: UL-listed compatible event printer. Dot-matrix, trac-
tor-fed paper, 120 VAC.
PRT-PK-CABLE: Programming cable. Used to update the
FACP’s flash firmware. (Also requires an RS485 to RS232
converter).